Question 1
Topic: Data Center and Critical Facilities Fundamentals
Skill tested: Selects facility redundancy levels that meet availability and maintenance requirements.
A regional data center supports a workload that must remain available during planned maintenance of a single power component. The design team is comparing distribution architectures. The facility can tolerate a single component failure without losing the protected load, but a fully duplicated end-to-end power train would exceed its capital budget. Which design best matches the stated requirement?
N+1 provides the required capacity plus one additional component, allowing the system to withstand a single component loss or remove one component for maintenance, subject to the design and switching arrangements. N has no spare capacity, so a component outage can affect the load. 2N duplicates the full system and offers greater fault tolerance but exceeds the stated budget and requirement. 2N+1 adds further redundancy to two complete systems and is still more extensive.